Application

Zone 1 and Zone 2 
Zone 21 and Zone 22 
Meet the necessities in the following industries, such as petroleum, chemical, electricity, medicine, textile, wine-making, aerospace, military, fire-fighting, etc.

Features

Features and benefits 
◆ Explosion protection to 
-CENELEC 
-IEC 
◆ GRP enclosure (glass fibre-reinforced polyester resin). 
◆ Seven types of enclosure.
 

Catalogue number logic



 

Note:

1. Please refer to the Selection Table on P25. 
2. Please select intermal components as below: 
HL0101 explosion-proof control button selection table on P32/36 
(nominal contact is 1NO+1NC); 
HL0102 explosion-proof indicator switch selection table on P38/39; 
HL0101-S explosion-proof control switch selection table on P34; 
Explosion-proof ammeter / voltmeter. 
3. Example: HLBX03-A2D2G 
Components: Two control buttons, two indicators;surface type 
Tech.Details: One start control button (HL0101-A1I02, 1NO+1NC); 
One stop control button (HL0101-A1I22, 1NO+1NC); 
One indicator (HL0102-G03, 230V AC); 
One indicator (HL0102-R03, 230V AC); 
4. Special requirements on request

echnical data

Explosion-proof control stations HLBX03(GRP)
  Explosion protection  
     Gas explosion protection             II2 G Ex de  IIC T6 Gb
     Dust explosion protection              II2 D Ex tb IIC T80℃ Gb ΙP66
  Conformity to standards      EN 60079-0:2012,EN60079-1:2007,EN60079-7:2007,EN60079-31:2009
       IEC 60079-0:2011,IEC60079-1:2007,IEC60079-7:2006,IEC60079-31:2008
  Enclosure Material      GRP(glass fibre-reinforced polyester resin)
  Enclosure colour      Black
  Exposed fastener      Stainless Steel
  Rated voltage      Max.415V AC
  Rated current      6A
  Degree of protection      IP66
  Ambient temperature      -40℃~+55℃
  Components      1.HL0101 explosion-proof control button technical data on P32/36;
       2.HL0102 explosion-proof indicator technical data on P38/39;
       3.HL0101-S explosion-proof control switch technical data on P34;
       4.Explosion-proof ammeter/voltmeter.
  Cable entries      M□×1.5 plug
  Mounting      Surface type
       Pole type (for enclosure Ⅰ,Ⅱ,Ⅲ, Ⅳonly)
  Note      1.Please specify the number and size of entries (applicable for surface type only);
       2.For pole type,only G1" entry is applicable;

 

Control station HLBX03(GRP) selection table

Dimension drawings (all dimension in mm) - subject to alteration

Dimension drawings (all dimension in mm) - subject to alteration

      Operation head h(mm)
      Frame 11
      Standard button 18
      Double button 18
      Button with key 40
      Emergency self-locked button 40
      Mushroom head button 32
      Mushroom head with key 46
      Signal lamp 18
      Button with lamp 18
      Control switch 1# 29
      Control switch 2#、3# 32
-- --
 